Patrik Různé 18. 3. 2022 13:18 18. 3. 2022 12:41

Na CP2000 LTE nechce fungovat sim od O2 SK. Operator code si nacita spravne ale IP nedostane.

V logu sa toto opakuje 

2022-03-16 14:40:26.341144 WDT: Starting modem [ppp0] ...

2022-03-16 14:40:26.479368 --> Sending: ATDT*99# 857 652

2022-03-16 14:40:26.482107 --> Waiting for carrier.

2022-03-16 14:40:26.587531 ATDT*99# 857 652

2022-03-16 14:40:26.588326 NO CARRIER

2022-03-16 14:40:26.588945 --> No Carrier!  Trying again.

FW mam aktualne verziu 5.0

Telekom SIM fungovala v poriadku.

Odpovědi 4

M.B. 17. 3. 2022 10:46

Prosím zkontrolujte zda je modem správně nastaven parametr Dialed Number, tak aby odpovídal požadavkům operátora.

Patrik 17. 3. 2022 11:14

dialed number bymal byt spravny, no nefunguje to aj tak

Udaje od operatora:

Základné nastavenia modemu pre pripojenie na internet sú: Inicializačný reťazec: at+cgdcont=1,"IP","o2internet" Telefónne číslo: *99***1#

log z CP

2022-03-17 11:06:31.145155 ==> Sending: ATE1

2022-03-17 11:06:31.808769 OK

2022-03-17 11:06:31.872184 ==> Sending: AT+CMEE=2

2022-03-17 11:06:32.567489 OK

2022-03-17 11:06:32.664207 ==> Sending: AT+CPIN?

2022-03-17 11:06:33.336903 +CPIN: READY

2022-03-17 11:06:33.449530 ==> Sending: AT+COPS?

2022-03-17 11:06:34.122303 +COPS: 0,2,"23106",7

2022-03-17 11:06:37.595228 ==> Manufacturer: Huawei Technologies Co., Ltd.

2022-03-17 11:06:37.659735 ==> Model: ME909s-120 V2

2022-03-17 11:06:38.010397 ==> Revision: 11.617.24.00.00

2022-03-17 11:06:38.197525 ==> IMEI: 868986040550809

2022-03-17 11:06:38.366142 ==> ICCID: 8942104323001647524

2022-03-17 11:06:38.536739 ==> IMSI: 231061131065713

2022-03-17 11:06:38.687536 ==> RSSI: -51 dBm

2022-03-17 11:06:38.821327 ==> OperatorName: Unknown

2022-03-17 11:06:39.102440 ==> OperatorCode: 23106

2022-03-17 11:06:39.380480 ==> OperatorMode: Automatic

2022-03-17 11:06:39.628440 ==> OperatorTech: E-UTRAN

2022-03-17 11:06:39.766890 ==> AccessTechnology: LTE

2022-03-17 11:06:39.906993 ==> MobileCountryCode: 231

2022-03-17 11:06:40.036201 ==> MobileNetworkCode: 06

2022-03-17 11:06:40.186750 ==> AbsRadioFreqChannel: 1679

2022-03-17 11:06:40.354712 ==> CellIdentity: EE5005

2022-03-17 11:06:40.507080 ==> PhysicalCellID: 160

2022-03-17 11:06:41.201524 ==> TrackingAreaCode: CB85

2022-03-17 11:06:41.960856 ==> RefSignalRecvPower: -79 dBm

2022-03-17 11:06:42.773755 ==> RefSignalRecvQuality: -10 dB

2022-03-17 11:06:43.567885 ==> RecvSignalStrength: -49 dBm

2022-03-17 11:06:44.183451 ==> PIN: READY

2022-03-17 11:06:44.676523 ==> Test: OK

2022-03-17 11:06:44.917777 --> WvDial: Internet dialer version 1.61

2022-03-17 11:06:45.009795 --> Initializing modem.

2022-03-17 11:06:45.112407 --> Sending: ATZ

2022-03-17 11:06:45.542462 ATZ

2022-03-17 11:06:45.543131 OK

2022-03-17 11:06:45.552993 --> Sending: AT+CGDCONT=1,"IP","o2internet"

2022-03-17 11:06:45.654313 AT+CGDCONT=1,"IP","o2internet"

2022-03-17 11:06:45.655431 OK

2022-03-17 11:06:45.655738 --> Sending: AT^LEDCTRL=1

2022-03-17 11:06:45.771336 AT^LEDCTRL=1

2022-03-17 11:06:45.772921 OK

2022-03-17 11:06:45.773923 --> Modem initialized.

2022-03-17 11:06:45.781290 --> Sending: ATDT*99***1# 857 652

2022-03-17 11:06:45.782469 --> Waiting for carrier.

2022-03-17 11:06:45.886053 ATDT*99***1# 857 652

2022-03-17 11:06:45.886788 NO CARRIER

2022-03-17 11:06:45.897860 --> No Carrier!  Trying again.

2022-03-17 11:06:46.102532 --> Sending: ATDT*99***1# 857 652

2022-03-17 11:06:46.103449 --> Waiting for carrier.

2022-03-17 11:06:46.211934 ATDT*99***1# 857 652

2022-03-17 11:06:46.212279 NO CARRIER

M.B. 17. 3. 2022 14:58

Problém je způsoben tím, že se za číslo *99***1# dostaly další čísla 857 a 652 a ty se zapsaly do konfigurace modemu. Při zpětném načtení do webové stránky tyto hodnoty však již nejsou vidět a nelze je zeditovat, protože jsou od zbytku odděleny mezerou.

Jediný způsob jak se jich aktuálně zbavit, je číslo ve formuláři zcela vymazat a konfiguraci odeslat do PLC. Ve formuláři se pak objeví první čislo za mezerou. Když se tento postup zopakuje, objeví se číslo 652, které už je možné nahradit správným číslem *99***1#.

Po této úpravě by modem měl opět pracovat. V logu by pak mělo být pouze Sending: ATDT*99***1#

Patrik 18. 3. 2022 12:41

Ďakujem, toto problém vyriešilo.

Tento dotaz je vyřešený.